D324 / E25-6        Double Inlet , 1600 CFM      220V   1N~   50Hz
 Performance



Air Volume [C.F.M]

Air Volume [m³/h]





Diagram is based on standard air p=1.2 kg/m³
Pd is system Curve for dynamical Pressure part
related to Fan Outlet Area (Curve for free blowing
fan).Total Pressure (the some of the dynamic and
static pressures) is shown in relation to the Air
volume, Dynamic pressure is shown below system
line Pd and static Pressure is shown above that
line.
Wheel Diameter = 230 mm = 9 in
35 Blades, 20mm =1" Chord Width
Tip Speed = rpm * 0.012 [m/s]
              = rpm * 2.37 [FPM]
Outlet Area = 0.076 [m²]=0.82[SQ.FT.]

Voltage
[V]
Air Volume [m³/h] @ p=1.2 kg/m³
Free
Air
Total Pressure Pt [Pa]
50 100 150 200 225 250
100 895 715 420    
170 1890 1780 1425 825 85    
220 2560   2200 1510 605 280 90


 Voltage Range
 Frequency
 Current max  @ free air
 Power  max   @ free air
 Speed            @ free air
  Insulation Class
  Protection Class
  Power Factor (cos ø )
•  Capacitor
  Net Weight
 Starting Torque
  Starting Current    max
  Air Temperature   max

100-220 [V]
50 [Hz]
2.1 [A]
420 [W]
750 [RPM]
H
IP65
0.90
10 [F] 400[V]
16.5 [kg]
1.5 [nm]
4 [A]
70 [°C]



Voltage
[V]
Sound Pressure Level dB(A)
100 170 220
Inlet 46 57 61
Outlet 47 58 62
    Measured in distance of 3m, @ free air






Copyright©2003 By Niroo Tahvieh Industries Co. All Rights Reserved