D324 / E25-6        Double Inlet , 1800 CFM      220V   1N~   50Hz
 Performance



Air Volume [C.F.M]

Air Volume [m³/h]





Diagram is based on standard air p=1.2 kg/m³
Pd is system Curve for dynamical Pressure part
related to Fan Outlet Area (Curve for free blowing
fan).Total Pressure (the some of the dynamic and
static pressures) is shown in relation to the Air
volume, Dynamic pressure is shown below system
line Pd and static Pressure is shown above that
line.
Wheel Diameter = 230 mm = 9 in
28 Blades, 25mm =1" Chord Width
Tip Speed = rpm * 0.012 [m/s]
              = rpm * 2.37 [FPM]
Outlet Area = 0.089 [m²]=0.96[SQ.FT.]

Voltage
[V]
Air Volume [m³/h] @ p=1.2 kg/m³
Free
Air
Total Pressure Pt [Pa]
50 100 150 175 200 225
100 1040 790 465    
170 2090 1970 1580 945 390    
220 2880   2410 1685 1135 500 150


 Voltage Range
 Frequency
 Current max  @ free air
 Power  max   @ free air
 Speed            @ free air
  Insulation Class
  Protection Class
  Power Factor (cos ø )
•  Capacitor
  Net Weight
 Starting Torque
  Starting Current    max
  Air Temperature   max

100-220 [V]
50 [Hz]
2.4 [A]
470 [W]
700 [RPM]
H
IP65
0.90
10 [F] 400[V]
17.5 [kg]
1.5 [nm]
4 [A]
70 [°C]



Voltage
[V]
Sound Pressure Level dB(A)
100 170 220
Inlet 46 57 62
Outlet 48 58 63
    Measured in distance of 3m, @ free air